Features | ● | 100% Pre-terminated and tested in factory to ensure transfer performance |
|
|
● | Fast to upgrade and reduces installation time |
● | Support 40G and 100G network applications |
|
Fiber Optic cable | ● | Tight buffer fiber OD: 900 ± 50 μm |
● | Cable colour: SM: Yellow colour OM1 & OM2: Orange colour OM3 & OM4: Aqua colour |
Type of Fiber Optic |
| SM(G.652.D, G.657 A1, G.657 A2), MM(OM1, OM2, OM3, OM4) |
Color Coding of Fiber Optic |
|  |
Polarity |
| Type-A, Type-B, Type-C (Refer to TIA/EIA-568-C.3 Array) |
Optical Performance |
| 
Note: 1. Test wavelength: SM@1310/1550 nm, MM@850/1300 nm; 2. Test method:compliant with IEC 61300-3-4 insertion B. |
Δ IL after 50 matings (for MPO/MTP) |
| ≤ 0.3 dB (refer to GR-1435) |
Δ IL after 500 matings (for LC/SC) |
| ≤ 0.2 dB (refer to IEC 61300-2-2) |
Mechanical characteristics | ● | Meet adhesion test requirement |
|
● | Meet salt mist test requirement |
|
Standard compliance |
| TIA/EIA-568-C.3, ISO/IEC 11801, IEC 61754-7, IEC 61754-4, IEC 61754-20, IEC 60794-1-2, IEC 60332-1, IEC 60332-3-24 |
RoHS |
| European Directive 2011 / 65 / EC RoHS Compliance |
Environment characteristics | ● | Installation Temperature: -10 °C to +60 °C |
|
● | Operation Temperature: -20 °C to +70 °C |
● | Storage Temperature: -20 °C to +70 °C |
|
Application | ● | Implementation of structured cabling in Data Center |
● | This cassette is only used for the standard enclosure |